Need help?

RPV HEPA XL

Illustration
Illustration
Application

Terminal filtration in air handling units for "CLEANROOM" applications

Application areas

  • Compact and economical
  • Large filtration area
  • High efficiency
  • Individual leak test on 0.3 µm at 0.45 m/s according to DIN 24.184 (from H13)
  • Individual MPPS efficiency test on 0.12 µm at 0.45 m/s (scanning test) according to EN182 standard
  • Individual test certificate provided with the filter (from H13)
  • Double labeling for traceability (from E10)
  • Tested for food contact according to CE 1935/2004
  • Certified inert to microbial growth (ISO 846-VDI 6022)
Certificates

General Characteristics

Filtration class EN1822: E12
Media: mini-pleated glass fiber paper
Frame: Polystyrene (SECURE)
Lut: polyurethane
Separators: hot-melt wire
Final pressure drop: 600 Pa
Maximum continuous service temperature: 80°C
Relative humidity: 70-80%
Contact our expert
  • RPV HEPA XL

    Illustration variation
  • E10

    • RPV100-6XL

    • Base A (mm)

      592

    • Height B (mm)

      592

    • Depth C (mm)

      440

    • Surface (m2)

      32

    • Airflow (m3/h)/Delta P (Pa)

      5000 / 160

    • Energy class

      A

    • RPV100-5XL

    • Base A (mm)

      592

    • Height B (mm)

      490

    • Depth C (mm)

      440

    • Surface (m2)

      27

    • Airflow (m3/h)/Delta P (Pa)

      4200 / 160

    • Energy class

      A

    • RPV100-3XL

    • Base A (mm)

      592

    • Height B (mm)

      287

    • Depth C (mm)

      440

    • Surface (m2)

      16

    • Airflow (m3/h)/Delta P (Pa)

      2500 / 160

    • Energy class

      A

  • E12

    • RPV120-6XL

    • Base A (mm)

      592

    • Height B (mm)

      592

    • Depth C (mm)

      440

    • Surface (m2)

      32

    • Airflow (m3/h)/Delta P (Pa)

      3400 / 25

    • Energy class

      A

* Energy consumption, kWh/year: calculated according to Eurovent Guideline 4/21-2018 | ** Energy class: according to Eurovent RS4/C/001-2019 | *** Energy class: according to Eurovent RS4/C/001-2015
Application areas

An air filtration system adapted to each sector

Illustration

Pharmaceutical Industry

Air filters ensuring safety adapted to pharmaceutical industry procedures

Discover all sectors
Illustration
TFM® Service

Choose TFM® and benefit from a comprehensive maintenance contract for air filtration.

Need clean air in your workplace? With the TFM® contract, you will benefit from high-performance air filters tailored to your needs, scalable services, and dedicated teams to advise you on the installation of new equipment.

Learn more about our service

Do you have any questions? Our team is here to help.

Our experts are available to answer all your questions.

Contact our expert
Illustration
Expert illustration

Hi, my name is Wannes Van Herck, how can I assist you?

Contact our expert